Condensate Pumps

Product Information

Pumps

Condensate Pump: Typically used when the condensate water has to be pumped out due to the drain pipes being installed above the unit. The type of condensate pump used will depend upon the amount of condensate generated by the unit, the amount of available space and the required pump pressure due to vertical discharge head and total tubing length. The equation below can be used to estimate the amount of condensate generated from a coil based on the latent load:
Ql = Latent Cooling Load
Condensate Generated (GPH) = 0.007884 x Ql

Price offers two condensate pumps to meet varying customer requirements:

Mini Condensate Pump: One of the quietest two-piece piston pumps on the market. This pump easily fits into the fan coil drain pan with minimal installation time and is ideal for units with tight space constraints.

Tank Pump: Designed for applications with higher flow and pressure requirements. These pumps are typically piped to the main drain pan connection.


Mini Condensate Pump (CMP)
Voltage 115V/240V
Max Flow rate 5.3 GPH
Max Suction Head 6.6 ft
Max Discharge head 20 ft
Noise Level in application (dB @ 3.3ft) <34
Electric Power 18W
Thermal Protection 194°F
Detection levels On=0.63”, Off=0.44”, Alarm=0.75”
Certifications UL/CSA
 
Dimensions L W H
Pump 2.6 1.7 2.4
Detection Unit 2.2 1.5 1.3
 
Pump Flow Rate (GPH)
Suction
Height (ft)
Vertical Discharge
Head (ft)
Total Tubing Length
16 ft 33 ft 66 ft 98 ft
0 3.3 5.02 4.63 4.1 3.57
6.6 4.63 4.23 3.7 3.17
10 4.23 3.7 3.17 2.64
13 3.7 3.17 2.65 2.46
16 3.04 2.64 2.46 1.85
20 -- 2.12 1.85 1.59
3.3 3.3 4.63 4.1 3.57 3.17
6.6 3.83 3.57 3.04 2.91
10 3.3 3.04 2.78 2.64
13 2.64 2.38 2.46 2.12
16 -- 1.98 1.72 1.46
20 -- 1.32 1.06 0.79
6.6 3.3 3.44 3.3 3.17 2.91
6.6 3.17 3.04 2.91 2.64
10 2.91 2.78 2.64 2.38
13 -- 1.98 1.85 1.59
16 -- 1.46 1.32 1.32
20 -- 0.93 1.79 0.79
 
Centrifugal Tank Pump (CTP)
Voltage 115V/240V
Max Flow rate 132 GPH
Max Discharge head 16 ft
Noise Level in application (dB @ 3.3ft) <47
Electric Power 40W
Thermal Protection 266°F
Detection levels On=0.94”, Off=0.51”, Alarm=1.18”
Certifications UL/CSA
 
Dimensions L W H
Pump 7.7 5.0 4.8
 
Pump Flow Rate (GPH)
Vertical Discharge
Head (ft)
Total Tubing Length
16 ft
33 ft
66 ft
98 ft
3.3
121
100
73
52
6.6
103
84
63
47
10
79
66
50
39
13
52
47
34
26
16
23
21
15
13