Models
Horizontal Concealed w/Plenum FCHCP
Factory assembled, horizontal blow-thru ducted FCHCP fan coils are designed for concealed installations above ceilings with ducted return and discharge air. They are suitable for projects such as hotels, motels, condominiums and general commercial applications.
| Standard Features Include: |
- AHRI 440 certified performance data.
- ETL-Listed. Constructed in compliance with ANSI/UL 1995 Standard.
- All casing sheet metal components fabricated of 20 gauge galvanized steel.
- Return air plenum thermally and acoustically insulated covering the motor(s)/blower(s) assembly to reduce noise generation from the unit.
- 1/2 in. (13) thick, min. 1.5 lbs. density
fiberglass internal insulation, which meets
NFPA 90A and UL181.
- Three speed permanent split capacitor (PSC) motor.
- 115, 208/240 and 277V motors available.
- Water coils with copper tubes and aluminum fins are performance rated and certified in accordance with the current edition of AHRI Standard 410.
- Coil manual air vents included.
- Single point power connector.
- Single wall painted steel drain pan, externally insulated.
- 1-Inch discharge air flange for discharge.
- 1-Inch MERV 3 return air filter.
|
|
|

| |
| Optional Features Include: |
- 1 through 4 row coils available for 2-pipe systems.
- 3 and 4 rows cooling coils with 1 or 2 row re-heat coils for 4-pipe system applications (6 rows max).
- LH or RH entry pipe connections.
- Single power supply disconnect switch and fuses.
- Drain pan options:
- Single wall drain pan manufactured in 20GA 304 Stainless
Steel externally insulated.
- Drain pan safety overflow connection (secondary drain).
- Hanger brackets.
- Insulation options:
- 5/8 in. thick Foil Faced fi berglass FB
- 1/2 in. thick Fiber Free FF 50.
|
|