Recommended Air Volume Ranges
CP 101
Unit
Size
L/s Min.* L/s Max.
cfm Min.*
cfm Max
4
5
6
7
8
9
10
12
14
16
24
30
31
47
62
108
126
173
226
315
106
165
212
307
378
496
637
991
1225
1649
50
63
70
100
130
170
262
300
370
500
225
350
450
650
800
1050
1350
2100
2600
3500

CP 100 & CP 200 Controller
Unit
Size
L/s Min.* L/s Max.
cfm Min.*
cfm Max
4
5
6
7
8
9
10
12
14
16
34
43
44
66
88
151
175
242
314
438
106
165
212
307
378
496
637
991
1225
1649
71
90
93
140
190
240
310
420
540
710
225
350
450
650
800
1050
1350
2100
2600
3500

Electronic or Digital Controls
Unit
Size
L/s Min.* L/s Max.
cfm Min.*
cfm Max
4
5
6
7
8
9
10
12
14
16
24
30
31
47
62
108
126
173
226
315
106
165
212
307
378
496
637
991
1225
1649
50
63
70
100
130
170
220
300
390
500
225
350
450
650
800
1050
1350
2100
2600
3500

Notes:
Factory calibrated controls must be selected within the above flow range limits. A minimum value of zero is also available. When an auxiliary flow setting is specified, the value must be greater than the minimum setting and within the range limits.

On controls mounted by Price but supplied by others, the air volume ranges are guidelines only.

*Minimum air ἀow limit is based on min .02" w.g. differential pressure signal from air flow sensor (.04" w.g. for CP100 and CP200). Selection of air flow limits below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supplied.