| Recommended Air Volume Ranges | ||||
| CP 101 |
|
Size |
L/s Min.* | L/s Max. |
|
|
| 4 5 6 7 8 9 10 12 14 16 |
24 30 31 47 62 108 126 173 226 315 |
106 165 212 307 378 496 637 991 1225 1649 |
50 63 70 100 130 170 262 300 370 500 |
225 350 450 650 800 1050 1350 2100 2600 3500 |
| CP 100 & CP 200 Controller |
|
Size |
L/s Min.* | L/s Max. |
|
|
| 4 5 6 7 8 9 10 12 14 16 |
34 43 44 66 88 151 175 242 314 438 |
106 165 212 307 378 496 637 991 1225 1649 |
71 90 93 140 190 240 310 420 540 710 |
225 350 450 650 800 1050 1350 2100 2600 3500 |
| Electronic or Digital Controls |
|
Size |
L/s Min.* | L/s Max. |
|
|
| 4 5 6 7 8 9 10 12 14 16 |
24 30 31 47 62 108 126 173 226 315 |
106 165 212 307 378 496 637 991 1225 1649 |
50 63 70 100 130 170 220 300 390 500 |
225 350 450 650 800 1050 1350 2100 2600 3500 |
| Notes: |
|
Factory calibrated
controls must be selected within the above flow range limits. A minimum
value of zero is also available. When an auxiliary flow setting is specified,
the value must be greater than the minimum setting and within the range
limits.
On controls mounted by Price but supplied by others, the air volume ranges are guidelines only. *Minimum air ἀow limit is based on min .02" w.g. differential pressure signal from air flow sensor (.04" w.g. for CP100 and CP200). Selection of air flow limits below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supplied. |