Models
Single Duct, High Pressure |
|
|
Constant Volume |
|
SH |
Variable Constant Volume |
|
SHV |
Constant Volume Heat Water Coil |
|
SHR |
Variable Constant Volume Heat Water
Coil |
|
SHVR |
Constant Volume Electric |
|
SHRE |
Variable Constant Volume Electric |
|
SHVRE |
|
|
 |
| |
|
|
| Features |
|
SH / SHV

SHR / SHVR

SHRE / SHVRE
 |
- Capacities ranging from 50 - 2500 cfm in 6 sizes.
- Design volume factory set to specified value within ± 5% of set-point (or 10 cfm below 200 cfm).
- Pressure independent operation from minimum operating static to 6 in. w.g.
- Leakage at regulator shut-off will not exceed 3% of maximum unit air volume at 6 in. w.g. inlet static pressure.
- Air volume reference scale provided to aid field adjustment.
- Terminals include a sound attenuator section.
- Unit casings up to and including size 14-24 are constructed of 22 gauge galvanized steel. All casings are insulated with
1/2 in. [13] insulation.
- Quick opening access panel provided as standard for inspection and service.
- Flanged rectangular outlet collar provided as standard.
- Optional 1 row or 2 row hot water coils are internally mounted. Coils are aluminum plate fin mechanically bonded to seamless copper tubes.
- Coil connections available either right or left hand.
- Optional electric coils are externally mounted. CSA certified flange type duct heater.
|
|