SPV, SDV Series

Product Information

View Performance Data SPV
General Information

Price has, as a primary component of its terminal unit line, the SPV (pneumatic controls), SDV (digital controls) single duct VAV assemblies. These units are designed to control the air flow rate of conditioned air into an occupied space in response to a control signal, usually a thermostat. The clean and efficient design of these single duct terminal units result in a system component which has minimal pressure drop reducing fan horsepower require­ments, and low noise generation for quiet operation. A compact configuration makes this unit easier to use in today‘s crowded mechanical spaces or in retrofitting existing systems.

Control options for this product line are wide and varied with pneumatic, analog electronic and state of the art direct digital control available to suit most any application. Most of the control options utilize the exclusive Price SP300 multipoint sensor for accurate duct air velocity pressure measure­ment. This allows the terminals to monitor the desired flow rate, as dictated by the thermostat, and com­pensate instantly for any changes in supply air pressure that might tend to alter the supply volume. In other words, the net result is a pressure indepen­dent variable air volume system.

In addition to the basic volume control assembly, a complete line of accessories is offered to meet specific job
require­ments. Sound attenuators, multi-outlet adaptors and heating coils are all available. These are factory assembled to the basic assembly for ship­ment as an integrated unit
.

 

Model SDV


A Participating Corporation in the ARI 880 Certification Program.

   
Features:    
  • Capacities ranging from 50 – 8000 cfm in 11 sizes.
  • Pressure independent operation.
  • Can be used for VAV or constant volume applications.
  • Available with pneumatic, or direct digital controls.
  • Factory calibrated to job requirements.
  • Individually adjustable minimum and maximum air volumes – easily field adjusted.
  • SP300 multipoint flow sensor designed to maintain control accuracy indepen-dent of field installation conditions.
  • Gauge taps for flow measurement and balancing supplied with factory mounted pneumatic controls (optional for digital controls by others).
  • Conveniently accessible externally mounted controls.
    • Inlet connection bead offers a means for secure flex duct connections.
  • A full 2 in. inlet connection to secure flex and hard duct connections.
    • Full range of accessories available (i.e. coils, attenuators, etc.).
  • NEMA1 Protective metal shrouds for digital (by Price) controls. Protective metal cover optional for pneumatic controls.

 

  • Compact, lightweight design for ease of installation.
  • 22 gauge zinc-coated steel housing (optional 20 gauge available).
  • 1/2 in. [13] thick, min. 1.5 lb density fiberglass internal insulation meets requirements for NFPA90A and UL181. 3/4 in. [19] and 1 in. [25] insulation also available as an option.
  • Special liners and insulations available.
  • Damper blade constructed of two layers of heavy gauge galvanized steel with a sandwiched peripheral gasket of cross linked polyurethane foam to ensure tight seal and no damper deflection.
    • Plated damper shaft with position indicator is mounted in self-lubricating bearings.
  • Optional insulated access door 4 x 6 3/4" (102x171) attached with 4 screws or optional latches.
  • Discharge complete with slip and drive cleat duct connections.
  • Performance certified in accordance with the AHRI 880 certification program.
  • Units with factory-mounted high voltage components like transformers or disconnect switches are ETL certified to UL 873.
  • Selected product configurations are OSHPD seismic pre-approved, in compliance with CBC 2013 and IBC 2012.
    Product Selection Checklist

  1. Select Unit Inlet Size based on control and acoustic parameters.
  2. Select Control type (Pneumatic, Digital) based on system design.
  3. Select Accessories (Multi-Outlet Adaptor, Attenuator) as required.
  4. Select Reheat Coil, if required.
  5. Select Control Sequence based on system design.
The pdfs are best viewed with Adobe Reader. Download it now.
Adobe Reader

PRICE ONLINE CATALOG

 
RepresentativesAbout PriceCareersContact UsPrivacy PolicyLimited Warranty
Copyright ©2014, All Rights Reserved - Price Industries