FPV / FDV Series

Product Information

View Performance Data FPV/FDV
Features
  • Recirculating fan section operates only on a demand for heat from the space thermostat.
  • Primary air section controls are pressure independent on models FPV 8000, and FDV 5000.
  • Size 20 and 30 – 22 gauge construction (optional 20 gauge available)
  • Size 40-60 – 20 gauge construction.
  • Zinc-coated steel housing, mechanically sealed, leak-resistant.
  • 3/4 in. thick, min 1.5 lb density fiberglass internal insulation coated to prevent air erosion and meets requirements of UL 181 and NFPA-90A. Optional 1 in. [25] thick fiberglass insulation is also available.
  • Bottom access panel of fan section is easily removable for field service.
  • Motor assembly is mounted on vibration isolators. Fan and motor assembly removable as a unit.
  • Motors are 60 cycle, single phase, 115, 208, 240 or 277 VAC, lubricated, permanent split capacitor type.
  • ECM – electronically commutated motor available as an option.
  • Solid state speed controller for adjusting fan section air flow.
  • Units are ETL listed to meet UL1995 and CSA No. 236.
  • Dimensions for control shroud will vary for series 5000 units depending on the DDC controls supplier.
  • A 2 in. collar is provided for inlet duct connection.
 
Product Selection Checklist

  1. Select Unit Inlet Size based on control and acoustic parameters.
  2. Select Control type (Pneumatic, Digital) based on system design.
  3. Select Accessories (Discharge or Inlet Attenuator) as required.
  4. Select Reheat Coil, if required.
  5. Select Control Sequence based on system design.

A Participating Corporation in the
AHRI 880 Certification Program.


Standard Motor Data   ECM Motor Data
Unit Motor Full Load Amps
Size H.P. 115V 208V 240V 277V

20

1/8

2.9

0.9

0.8

1.1

30

1/4

4.7

0.8

0.7

1.7

40

1/2

9.8

3.8

3.8

3.2

50

3/4

12.3

5.4

5.2

4.4

60
1
--
6.5
7.8
7.8
 
Unit Motor Full Load Amps
Size H.P. 115V 240V 277V

20

1/3

3.9

1.9

1.6

30

1/2

7.7

3.5

3.0

40

1/2

7.7

3.5

3.0

50

1

12.6

6.1

5.4

60

1

12.6

6.1

5.4

     
Product Key    
     
Product Overview

Variable Volume/Parallel Flow
Fan Powered Terminal Units
With the variable volume model, the conditioned primary air does not pass through the fan. The primary air section and the recirculating fan section operate independent of each other, except that both are under control of the same room thermostat. They are sequenced so that both sections generally do not operate at the same time. The primary air section responds to a demand for cooling, while the recirculating fan section responds to a demand for heating.

Benefits of Variable Volume Fan
Powered Terminal Units

The primary air valve is sized for cooling demand similar to single duct terminal design requirements.
The recirculating air section is typically sized at 50% of the maximum primary air valve demand which results in lower noise, lower unit cost and reduced energy when compared to constant volume terminals
.

Construction:

 


Options:

  • Several other Price liner options available (FF - 3/4" fiber free foam, FB- 5/8" foil faced rigid fiberglass board, SM solid metal liner (dual wall) ,PM perforated metal liner, AFPM- foil faced fiberglass with perforated liner). See page F403-F404 for detailed information about Price liners selection.
  • ECM energy efficient motor option
  • Discharge attenuator section (DAS) for reduction of discharge noise
  • Inlet attenuator section (IAS) for reduction of radiated noise
  • Merv 8 and 13 filter bank for enhanced filtration of recirculated air
  • Hanger brackets and spring isolation.
  • Compact, durable zinc-coated steel casing
    means reduced ceiling plenum space requirements and protection from corrosion.
  • Terminal casing is internally lined with fiberglass insulation. The insulation's high density skin provides erosion resistance while effectively attenuating noise. Insulation meets requirements of UL181 and NFPA-90A.
  • Proven reliable primary air section with heavy gauge damper and low leakage blade seal.
  • PRICE terminals come standard with SCR fan speed control for efficient, quiet adjustment of fan capacity. Electric motors are specifically designed to operate with SCR controls ensuring reliable maintenance free operation.
  • Fan motor is isolated from the blower housing to reduce noise. Additional vibration isolators and heavy duty motor mounts are provided on large unit sizes.
  • Energy efficient, fan motor is designed to
    meet consistent torque specifications providing reliable and repeatable performance. ECM – Electronically Commutated Motors are available as an option.
  • Large removable bottom access panel provides access to the interior of the unit for cleaning, inspection and service.

Performance

 
  • Acoustical and flow performance is AHRI certified providing reassurance that design goals will be met and that Price fan powered terminal units will provide occupant comfort and efficient operation.
 
Quality Assurance  
  • Each Price fan powered terminal unit receives a full operational check before shipment and arrives factory calibrated in accordance with project specifications. This means costly labor and setup delays are avoided.
  • Units are certified in accordance with the AHRI 880 certification program.
  • Units are ETL listed to meet UL1995 and CSA No. 236.
   