FPC, FDC Series

Product Information

View Performance Data FPC/FDC

Design Features
Price constant volume fan powered terminal units offer several significant advancements beneficial to the building owner, consulting engineer and installing contractor.

Features such as advanced sensor technology, low noise levels, wide product size and flow range, increased hot water coil selection and new innovative options establish Price as an industry leader for terminal units.

Price SP300 Sensor
The Price SP300 velocity pressure sensor is a multipoint center averaging device which provides improved accuracy at low flow conditions. Accurate flow measure­ment and control is maintained even with poor inlet duct conditions. The sensor is designed and constructed with an aerodynamic profile to reduce noise level and pressure drop. Improved structural integ­rity prevents damage during installation.

Wide Product Range
Seven model sizes are available for greater selection flexibility. The seven sizes provide a wide air flow range from 100 cfm to 4000 cfm. Each size is designed with an optimized casing footprint. The efficient, compact construction reduces jobsite space requirements.

Coil Selection Flexibility
High capacity hot water coils provide greater selection flexibility. Sizes 20, 30, 40, 50 and 60 are available with an oversize 1 row coil in addition to the standard 1 and 2 row offering. The oversized coil can be selected for higher heating capacity applications.

Options
Several innovative options are available with Price constant volume terminals. These include:

  • ECM motor technology providing the benefits of reduced energy con­sumption, factory set fan air volume and longer motor life.
  • Bottom access door with quarter-turn cam latch fasteners for quick removal.
  • An extensive choice of insulation liner systems. (FF, FB,SM,PM,AFPM).
  • Electric coils (EC)
  • Discharge attenuator section (DAS)
    for reduction of discharge noise
  • Inlet attenuator section (IAS) for reduction of radiated noise
  • Fresh Air Inlet (FAI) for control and monitoring of outdoor air
  • Merv 8 and 13 filter bank for enhanced filtration of recirculated air
  • Hanger brackets and spring isolation selection offers flexibility. Standard and oversized coils can be selected.

Model FDC 5000

SP300

A Participating Corporation in the AHRI 880 Certification Program.

 

 

Features: Standard Motor Data
  • Recirculating fan section operates continuously.
  • Primary air section controls are pressure independent.
  • Zinc-coated steel housing, mechanically sealed, leak-resistant construction.
  • Size 10, 20, 30 – 22 gauge construction (optional 20 gauge available).
  • Size 40, 50, 60, 70 – 20 gauge construction.
  • 3/4 in. [19] thick, min. 1.5 lb density fiberglass internal insulation which meets requirements of UL 181 and NFPA-90A. R value = 2.8.
  • Bottom access panel of fan section is easily removable for field service.
  • Motors are 60 cycle, single phase, 115, 208, 240, 277 VAC lubricated, permanent split capacitor type.
  • ECM – electronically commutated motor available as an option.
  • Motor assembly is mounted on vibration isolators. Fan and motor assembly removable as a unit.
  • Solid state speed controller, SCR for adjusting fan section air flow.
  • Certified in accordance with the AHRI 880 certification program.
  • Units are ETL listed to meet UL1995 and CSA No. 236.
  • A 2 in. collar is provided for inlet duct connection.
Unit Motor Full Load Amps
Size H.P. 115V 208V 240V 277V

10 1/10 2.1 N/A N/A N/A
20 1/8 2.9 1.0 0.9 1.1
30 1/4 6.4 1.1 1.0 2.7
40 1/2 11.2 4.3 4.3 4.0
50 3/4 12.2 5.4 5.2 5.0
60 1 -- 6.5 8.2 8.2
70 2x3/4 23.2 8.6 8.6 9.4
 
ECM Motor Data
Unit Motor Full Load Amps
Size H.P. 115V 240V 277V

10 1/3 1.8 0.9 0.7
20 1/2 3.5 2.0 1.5
30 1/2 6.4 3.2 3.3
40 1/2 7.2 3.2 2.7
50 1 11.8 5.8 5.3
60 1 11.8 5.8 5.3
70 2x3/4 20 9 9

 

 

    Product Selection Checklist

  1. Select Unit Inlet Size based on control and acoustic parameters.
  2. Select Control type (Pneumatic, Electronic, Digital) based on system design.
  3. Select Accessories (Inlet or Outlet, Attenuator) as required.
  4. Select Reheat Coil, if required.
  5. Select Control Sequence based on system design.