The Price FDCOA is a Series Flow Fan
Powered terminal unit specifically designed
for operation with a Dedicated Outdoor Air
System (DOAS). In this configuration the
DOAS air handler is selected to dehumidify
and condition the outdoor air as well as to
handle the space latent load. The primary
valve of the FDCOA terminal is supplied
from the DOAS and controls the amount
of fresh air to the space. A cooling coil
mounted to the return air inlet is selected to
handle the space sensible cooling load. An
optional MERV 3, 8, or 13 filter is available
for enhanced indoor air quality. For zones
requiring heat an optional electric or hot
water coil is available. The FDCOA is supplied
as standard with an energy efficient ECM
motor programmed with the Price Enersave
constant flow program to compensate for
filter loading.
The Price FDCOA terminal offers substantial
benefits over a conventional VAV system.
Hydronic cooling is far more efficient than
delivering cooled air to a zone and chilled
water piping takes up a fraction of the space
of ductwork. By taking care of the space
sensible load with the FDCOA cooling coil
the DOAS air handler can be sized to deliver
only the airflow required for ventilation and
latent loads. This air flow reduction results in
a smaller HVAC system which translates into
fan energy savings. A smaller HVAC footprint
and ductwork can also reduce floor heights
or increase leasable space. Decoupling the
sensible and latent loads ensures proper
humidity control at each zone. Additionally
the exact outdoor air requirements to each
zone can be maintained, eliminating over
ventilation and ensuring compliance with
ASHRAE 62. Further energy savings can
be realized if a Demand Control Ventilation
(DCV) strategy is utilized. |
| |
| Features: |
- Recirculating fan section operates
continuously during occupied mode.
- Low profile casing for restricted ceiling
spaces.
- Primary air section controls are pressure
independent.
- VAV inlet valve equipped with Price
SP300 air flow sensor and a low leakage
damper.
- Zinc-coated steel housing, mechanically
sealed, leak-resistant construction.
- 1/2 in. [12] thick, min. 1.5 lb density
fiberglass internal insulation which
meets requirements of UL 181 and
NFPA-90A. R value = 1.9.
- Large (1 to 6 row) sensible cooling coil at
the return air inlet with galvanized drip
pan. The sensible cooling coil is intended
for dry operation only.
- Water coils are performance rated and
Certified to AHRI Standard 410.
- Large face, low velocity MERV 3 filter.
- Bottom access panel of fan section is
easily removable for field service.
- ECM Motors – electronically commutated
- 60 cycle, single phase, 115, 208, 240,
277 VAC.
- Motor assembly is mounted on vibration
isolators. Fan and motor assembly
removable as a unit.
- Solid state speed controller, SCR for
adjusting fan section air flow.
- Certified in accordance with the AHRI
880 certification program.
- Units are ETL listed to meet UL1995 and
CSA No. 236.
- A 2 in. collar is provided for inlet duct
connection.
|
|
|
Typical FDCOA installation |
|
|
|
|
|
Perimeter slot diffusers and chilled beams |
|
|
|
|
|
|
| |
ECM Motor Data 
| Unit |
Motor |
Full Load Amps |
| Size |
H.P. |
115V |
240V |
277V |
|
| 10 |
1/3 |
3.7 |
2.2 |
1.7 |
| 30 |
1/3 |
4.7 |
2.8 |
2.3 |
| 40 |
1/2 |
6.6 |
3.9 |
3.3 |
| 60 |
2x1/2 |
9.6 |
4.5 |
4.2 |
|
 |
|
|
A Participating Corporation
in the AHRI 880 Certification Program. |
|
| Optional Features: |
|
Product Selection Checklist
|
|
- Select Unit Inlet Size
based on control and acoustic parameters.
- Select Control type (Pneumatic,
Digital) based on system design.
- Select Accessories (Inlet or Outlet, Attenuator)
as required.
- Select Reheat Coil, if
required.
- Select Control Sequence
based on system design.
|
|
|
- 1 or 2 row hot water coils or electric coils
- Stainless steel drain pan
- Liner options:
- Solid Metal
-
Perforated Metal
-
Foil Face Fiberglass
-
Fiber Free Foam
- MERV 3, 8 or 13 return air filter for
improved IAQ and LEED credit.
|
|